Mains Input Electrical Specifications; Bypass Input Electrical Specifications - Huawei UPS5000-E-30 kVA-FM User Manual

Table of Contents

Advertisement

UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
Item

7.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage range
Rated frequency
Input frequency range
Input power factor
THDi

7.6 Bypass Input Electrical Specifications

Item
Rated input voltage
Input voltage range
Issue 03 (2022-01-30)
Specifications
Voltage dip and temporary
interruption
Specifications
380 V AC/400 V AC/415 V AC (line voltage)
Upper threshold: +10%, +15% (default), +20%,
+25% (when the voltage system is 380 V AC)
Upper threshold: +10%, +15% (default), +20%
(when the voltage system is 400 V AC)
Upper threshold: +10% (default), +15% (when the
voltage system is 415 V AC)
Lower threshold: –10%, –15%, –20% (default), –
30%, –40%, –50%, –60%
Copyright © Huawei Technologies Co., Ltd.
IEC 61000-4-11
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
● At 30–40°C: The UPS works at full load when
the voltage is 187–280 V AC and is derated
to 40% load when the voltage is 187–80 V
AC.
● At 0–30°C: The UPS works at full load when
the voltage is 176–280 V AC and is derated
to 40% load when the voltage is 176–80 V
AC.
50 Hz/60 Hz
40–70 Hz
● > 0.99 (full load)
● > 0.98 (half load)
● ≤ 3% (linear load)
● ≤ 5% (non-linear load)
7 Technical Specifications
122