Huawei UPS5000-E-30 kVA-FM User Manual page 58

Table of Contents

Advertisement

UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
Item
Ground
cable
Table 3-3 Power cable terminal requirements
Port
Mains
input
Bypass
input
Issue 03 (2022-01-30)
Recommende
d cross-
sectional area
2
(mm
)
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
When the external conditions change, for example, the cable layout or
ambient temperatures, perform verification in accordance with the
IEC-60364-5-52 or the local regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage
is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
When the mains input and bypass input share a power source, configure input
power cables as mains input power cables. In addition, cables listed in
3-2
apply only to the following conditions:
The cables are installed along the wall or on the floor (IEC-60364-5-52 C
standards).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%. The recommended cable diameters in
through-current requirements. Users should evaluate the line voltage loss
based on the actual cable length. If the voltage loss exceeds the
requirements, increase the cable diameter properly.
Single- or multi-core 90°C-resistant copper flexible cables are used.
Connection
Method
Crimped OT
terminals
Crimped OT
terminals
Copyright © Huawei Technologies Co., Ltd.
Specifications
30 kVA
PE
10
Bolt
Bolt Hole
Specifications
Diameter
M10
11 mm
M10
11 mm
3 Installation
60 kVA
90 kVA
16
35
Table 3-2
meet the basic
Bolt Length
30 mm
30 mm
120 kVA
50
Table
Torque
26 N·m
26 N·m
50