Clearing The Epo State; Exporting Data - Huawei UPS5000-E-30 kVA-FM User Manual

Table of Contents

Advertisement

UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
After you press the EPO button, the EPO and No power supplied alarms are
displayed on the LCD.

4.10 Clearing the EPO State

Procedure
Step 1 Clear the EPO state. Ensure that the EPO button connected to the dry contact is
not in the EPO state.
Step 2 Clear the EPO alarm.
Step 3 Check that the EPO alarm is cleared by viewing active alarms. If the system bypass
input is normal, the UPS transfers to bypass mode.
Step 4 Start the inverter.
----End

4.11 Exporting Data

The following data can be exported:
Web
1.
Issue 03 (2022-01-30)
On the LCD
On the LCD, choose System Info > Alarms and tap Clear Faults. In the
displayed dialog box, tap Yes. The EPO alarm is cleared successfully.
On the WebUI
Choose Monitoring > UPS System > Running Control and click Clear Fault.
The EPO alarm is cleared.
On the LCD
Choose System Info > Alarms > Active Alarms to check that the EPO alarm
is cleared.
On the WebUI
Choose Home > Active Alarm to check that the EPO alarm is cleared.
Historical alarms
Active alarms
Performance data
Operation logs
NO TE
This procedure describes how to export historical alarms.
Choose Query > Export Data > Export Historical Data. Set Encryption
Password for Export, and select Historical Alarm from the Data Type drop-
down list.
Copyright © Huawei Technologies Co., Ltd.
4 Operations
107