7.8 Output Electrical Specifications
Item
Output system
Voltage
THDv
Output PF
Transfer time
Output voltage unbalance
Issue 03 (2022-01-30)
Copyright © Huawei Technologies Co., Ltd.
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC±1% (line voltage)
● THDv ≤ 1% (100% linear load)
● THDv ≤ 3% (100% non-linear load)
1
● 0 ms (uninterruptible transfer)
● Interruptible transfer: ≤ 20 ms
Voltage unbalance: ±3%, phase unbalance:
120±2°