Huawei UPS5000-E-30 kVA-FM User Manual page 57

Table of Contents

Advertisement

UPS5000-E-(30 kVA–120 kVA)-FM
User Manual
Item
Bypass
input
Output
Battery
input
(lead-
acid
battery)
Issue 03 (2022-01-30)
Recommende
L1
d cross-
L2
sectional area
2
(mm
)
L3
N
Bypass input current (A)
Recommende
L1
d cross-
L2
sectional area
2
(mm
)
L3
N
Output current (A)
Recommende
U
d cross-
V
sectional area
2
(mm
)
W
N
(When
the UPS
connect
s to a
non-
linear
load,
increase
the
cross-
section
al
area.)
Nominal discharge
current (A)
Maximum discharge
current (A)
Recommende
+
d cross-
N
sectional area
2
(mm
)
-
Copyright © Huawei Technologies Co., Ltd.
Specifications
30 kVA
60 kVA
4 x 10
4 x 35
45
91
4 x 10
4 x 25
45
91
4 x 10
4 x 25
66
132
79
158
3 x 16
3 x 50
3 Installation
90 kVA
120 kVA
4 x 70
4 x 95
136
182
4 x 50
4 x 70
136
182
4 x 50
4 x 70
197
263
236
315
3 x 70
3 x 120
49

Advertisement