7-13 Digital Keypad–KPC-CC01, KPC-CE01
7-13-1 Keypad Panel introduction
The default communication protocol for ME300 is ASCII 9600, 7, N, 2, whereas the default
communication protocol for KPC-CC01 is RTU 19200, 8, N, 2. So you must set the ME300
communication parameters as follows to connect it to KPC-CC01.
Pr.09-00 Communication Address: Settings = 1
Pr.09-01 COM1 Transmission Speed (Baud rate): Settings = 19.2 Kbps
Pr.09-04 COM1 Communication Protocol: Settings = 13: 8N2 (RTU)
KPC-CC01
Keypad Functions Description
Key
Start Operation Key
1. Only valid when the source of operation command is the keypad.
2. Operates the AC motor drive by the function setting. The RUN LED will be ON.
3. Can be pressed repeatedly at the stop process.
Stop Command Key.
1. This key has the highest priority when the command is from the keypad.
2. When it receives the STOP command, regardless of whether the AC motor drive is in
3. Use the RESET key to reset the drive after a fault occurs.
4. If you cannot reset after the error:
Operation Direction Key
1. Only controls the operation direction, NOT the drive activation. FWD: forward, REV: reverse.
2. Refer to LED Descriptions for more details.
KPC-CE01
operation or stop status, the AC motor drive executes the "STOP" command.
a. The condition which triggers the fault is not cleared. After you clear the condition, you
can then reset the fault.
b. The drive is in fault status when powered on. After you clear the condition, restart and
then you can reset the fault.
Chapter 7 Optional AccessoriesME300
Communication Interface
RJ45 (socket), RS-485 interface
Communication Protocol
RTU19200, 8, N, 2
Installation Method
Install the embedded type on the surface of the
control box. The front cover is waterproof.
Buy a MKC-KPPK model for wall mounting or
embedded mounting. Its protection level is IP66.
The maximum RJ45 extension lead is 5 m (16 ft)
This keypad can only be used on Delta's motor
drive C2000, CH2000, CP2000, MS300, MH300,
and ME300.
Descriptions
7-55