User's Manual
6. Start up
Before to supply the thyristor unit:
• verify that load current equal or less than nominal;
For resistive load
P
I
=
tot
V
3
• verify that there is no short circuit on load;
• verify that main voltage equal or less than nominal;
• verify that all auxiliary connections are right;
• fan voltage equal than nominal (230V std , 110V optional)
After which supply thyristor unit giving the maximum i n put signal and verify that load current is
equal or less than thyristor unit nominal current.
Warning: this procedure can be done just by specialized personnel.
The
thyristor
requirements. If it's necessary to change on site the configuration, procede as below
specified.