5.2 Cabling detail

Use 75°C copper (CU) conductor only, provided with the terminal type indicated below.
Current/courant
125A, 150A,
200A, 225A
275A
400A
450A, 500A
600A, 700A
www.cdautomation.com
CD3000S-2PH from 125A to 700A
Torque/couple
Lb-in (N-m)
310 (35.0)
372 (42.0)
505 (57.0)
14
Wire Range/cable
18 - 600kcmil
Bus Bar
C.D. Automation Srl
Wire
Terminal/terminal
Polymeric Terminal
Block M8
Bus Bar Adapter M8
Bus Bar Adapter M10