3.11
Special safety instructions (North America, Terra AC Wx-
P8-xxxxx)
3.11.1
Important safety instructions (North America, Terra AC Wx-P8-
xxxxx)
•
Read all the instructions befor you use this EVSE.
•
Make sure that adults supervise this EVSE is when it is used around children.
•
Do not put fingers into the EV connector.
•
Do not use this product if the flexible power cord or EV charge cable is frayed,
has broken insulation, or any other signs of damage.
•
Do not use this EVSE if the enclosure or the EV connector is broken, cracked,
open, or shows any other indication of damage.
•
Install an insulated grounding conductor that is identical in size, insulation
material, and thickness to the grounded and ungrounded branch-circuit supply
conductors, except that it is green with or without one or more yellow stripes,
as part of the branch circuit that supplies the EVSE.
•
Connect the grounding connector of the previous bullet point to earth at the
EVSE or, when supplied by a separately derived system, at the supply
transformer.
BCM.V3Y00.0-EN | 002 - DRAFT
Warning: Obey the basic precautions for electric products, including the
instructions in this section.
Caution: To reduce the risk of fire, connect this EVSE only to a circuit
provided with 40 A maximum branch circuit overcurrent protection in
accordance with the National Electrical Code, ANSI/NFPA 70.
Safety
31