ESIE19-06
|
Part 5. Appendix
11. After you have completed all the changes, press the Cancel button (a) twice to return to the normal mode.
List of the settings
Setting
Setting
Setting
switch
mode
description
no.
Filter
contamination
contamination
0
inspection
check with fan
setting
step 1-15
1
Low tap setting
Supply fan step
2
Step 1
setting*
Exhaust fan
3
Step 1
step setting*
24 hour
4
ventilation
setting
19(29)
Reference
concentration
7
shift for
ventilation flow
control (ppm)
Stop ventilation
by automatic
Allowed
ventilation air
8
flow control
Fan residual
operation
Normal
ventilation tap
9
on automatic
ventilation air
flow control
Fresh-up
1A
0
operation**
Page 64
Setting position no.
01
02
03
Filter
Filter
contamination
Timer based
check with
check
new fan step
Run 1/15
Run 1/10
Off
(28 min. off/
(27 min. off/
2 min. on)
3 min. on)
Step 2
Step 3
Step 2
Step 3
Run 1/15
Run 1/10
Off
(28 min. off/
(27 min. off/
2 min. on)
3 min. on)
0
+200
+400
NOT Allowed
Allowed
Heater
Off
Off
operation
Off
On
Modular L Smart
04
05
06
Auto ESP
Target
selection +
detection filter
target
with fan step
detection filter
1-15
with new fan
step
Run 1/6
Run 1/4
Run 1/3
(25 min. off/
(22.5 min. off/
(20 min. off/
5 min. on)
7.5 min. on)
10 min. on)
Step 4
Step 5
Step 6
Step 4
Step 5
Step 6
Run 1/6
Run 1/4
Run 1/3
(25 min. off/
(22,5 min. off/
(20 min. off/
5 min. on)
7,5 min. on)
10 min. on)
+600
-200
-400
NOT Allowed
Heater
operation
Control by
CO
sensor
2
Setting position no.
07
08
09
10
11
12
Continuous operation
Run 1/2
(15 min. off/
Step
Step
Step
Step
Step
15 min. on)
1
2
3
4
5
Step
Step
Step
Step
Step
Step 7
8
9
10
11
12
Step
Step
Step
Step
Step
Step 7
8
9
10
11
12
Continuous operation
Run 1/2
(15 min. off/
Step
Step
Step
Step
Step
15 min. on)
1
2
3
4
5
-600
21/01/20
5.1. Field setting
13
14
15
Step
Step
Step
6
7
8
Step
Step
Step
13
14
15
Step
Step
Step
13
14
15
Step
Step
Step
6
7
8
|
Version 1.1