Daikin Modular L Smart Service Manual page 22

Hide thumbs Also See for Modular L Smart:
Table of Contents

Advertisement

ESIE19-06
|
Part 2. Troubleshooting
Error code
Main
Sub
C6
35
flashing
C6
36
flashing
C6
37
flashing
CH
-
on
CJ
-
on
60
-
flashing
60
-
on
64
01
on
64
02
on
65
01
on
65
02
on
65
03
flashing
6A
-
on
6A
-
flashing
U5
-
flashing
U5
-
flashing
U8
-
flashing
UA
-
flashing
UC
-
on
UE
-
flashing
UE
-
on
Page 22
Modular L Smart
Unit
Error level
No.
flashing
flashing
error ①
(reset remote control)
flashing
flashing
error ①
(reset remote control)
flashing
flashing
error ①
(reset remote control)
off
off
warning
off
off
warning
flashing
flashing
error ②
(recover automati-
cally)
off
flashing
alert
off
flashing
alert
off
flashing
alert
off
flashing
alert
off
flashing
alert
flashing
flashing
error ①
(reset remote control)
off
flashing
alert
flashing
flashing
error ②
(recover automati-
cally)
flashing
flashing
error ②
(recover automati-
cally)
flashing
flashing
error ②
(recover automati-
cally)
flashing
off
error ②
(recover automati-
cally)
flashing
off
error ②
(recover automati-
cally)
off
off
warning
flashing
flashing
error ②
(recover automati-
cally)
off
flashing
alert
2.2. Error based troubleshooting
Operation state
Cause of error
stop fan operation
Exhaust air FAN ② (address 4)
(cause of fault)
EEPROM read abnormality
stop fan operation
Exhaust air FAN ② (address 4)
(cause of fault)
thermistor fault abnormality
stop fan operation
Exhaust air FAN ② (address 4)
(cause of fault)
fin temperature abnormality
keep running
CO
sensor warning
2
keep running
thermistor fault "BRC..."
user interface
stop operation
external error input
keep running
external error input
keep running
air return thermistor alert
keep running
out of operation range alarm due
to air return thermistor
keep running
outdoor air intake thermistor alert
keep running
out of operation range alarm due
to outdoor air thermistor
stop operation
low outdoor temperature opera-
tion alarm during filter contamina-
tion function (field setting
29-0-04/05)
keep running
damper alert
stop operation
damper error
stop operation
user interface transmission error
missing
stop operation
user interface control communica-
tion error
stop operation
transmission abnormality between
main/slave liquid crystal remote
control
stop operation
remote control combination failure
keep running
duplication of central group
address warning
stop operation
central control communication
error
keep running
central control transmission alert
21/01/20
|
Version 1.1