Installation Of Generator Set - Hyundai DHY18KSEm Operation And Maintenance Manua

Soundproof type diesel genset
Table of Contents

Advertisement

1~1.5  m  of  distance  from  the  generator  set  and 
1.5~2m above the generator set. 
◆The  generator  set  working  room  shall  be  furnished 
with  fire  extinguish  hydrant  which  conform  to  the 
specified standard. 
◆Emergency  lighting  facilities  shall  be  installed  in  the 
generator  set  working  room  for  the  convenience  of 
operation and maintenance. 
◆No  combustible  and  explosive  materials  are  allowed 
to be placed in the generator set working room. 
Below is the layout for the open system generator set 
working room. 
(Foundation drawing Refer to APPENDIX B ) 
 
 
Note:   
Our  company  can  make  drawings  and  design 
installation  dimensions  for  generator  set  working 
room according to customer's special requirements. 
 
Below is the layout for the canopy system generator 
set working room. 
(Foundation drawing Refer to APPENDIX C )
Note:   
Canopied  generator  set  can  work  outdoor  directly.  If 
users  wants  to  operate  the  generator  set  indoor, 
above  diagram  can  be  taken  as  reference.  we  can 
design the layout of generator set working room and 
installation dimension according to customer's special 
requirements. 
2.5
 Installation of Generator Set 
2.5.1 
Locate the position of generator set
Vibration  reduction  units  have  been  installed  on  our 
generator  sets  (except  a  few  generator  sets  don't 
have this kind of facility). Users can take reference on 
the  installation  diagram,  correctly  install  the 
generator set on a flat and hard foundation, use the 
expansion bolts to tightly fix the generator set to the 
concrete foundation through the installation holes on 
the  base  frame.  When  no  special  requirement  is 
needed,  we  don't  suggest  customers  to  install 
additional vibration reduction units. 
Soft connection is needed to connect the parts of the 
generator  set  to  outside.  For  example:  corrugated 
vibration  reduction  pipe  has  been  used  to  connect 
exhaust  pipes,  air  exhaust  path,  fuel  inlet  pipe,  fuel 
return  pipe  and  busbar  cable  etc.,  all  of  these  parts 
need to use soft connections. Only in this way we can 
reduce the adverse effect caused by the vibration of 
generator set to the minimum extent. 
2.5.2 
Ventilation     
When a generator set with a complete set of radiator 
assembly has been installed in the working room, the 
basic  principle  is  to  discharge  the  hot  air  in  the 
working  room  to  outside  and  let  in  the  low 
temperature  air  from  outside,  and  try  you  best  to 
avoid the hot air come in from outside. 
The diagram in the right side demonstrates the ideal 
position of a generator set in the working room. 
The  purpose  of  this  arrangement  is  to  get  cold  air 
from the lowest point as much as possible, and force 
them to pass through the radiator core, and then lead 
them out. 
 
 
Users  can  use  metal  plate  or  canvas  to  make  a  wind 
guide  cover,  the  connection  between  wind  guide 
cover  and  the  radiator  shall  be  soft  connection,  so 
that to cut off the transmission of vibration from the 
generator set, and also ensure the hot air exhaust to 
outside thoroughly. 
The  effective  circulation  sectional  area  inside  of  the 
wind  guide  cover  shall  be  bigger  than  1.25  times  of 
the front face area of the radiator core. And the wind 
guide  cover  shall  be  smooth,  no  sharp  angle  and 
camber so that to reduce the resistance to the wind. 
At  the  same  time,  the  effective  circulation  sectional 
area in the air inlet opening shall also be bigger than 
 
1.25 times of the front face area of the radiator core. 
When the users have installed mesh cover or shutters 
in  the  air  inlet  /outlet  opening  or  there  is  too  many 
cambers  in  the  air  inlet/outlet  opening,  the  effective 
air  circulation  sectional  area  will  be  reduced  and 
resistance  will  increase,  and  therefore,  it's  necessary 
to further increase air circulation area. 
5
User manual
                                                             
 