 Operation for control system 
3.6.1 
Generator control panel operation 
Our  generator  set  standard  supply  two  different 
control  module:  one  is  single  generator  with  remote 
start  function,  the  other  is  single  generator  with 
Automatic Mains Failture (with ATS panel) . 
Start‐up generator 
1) Set  every  circuit  breaker  and  switch  of  loads  to
"OFF"  position. 
2) Turn  the  Generator  set  Main  Circuit  Breaker  and
other circuit breakers to the  "OFF"  position. 
3) Connect the engine battery cable with battery.
4)
Turn on the panel power switch 1S1 (Ref. Appendix
D circuit diagram) to the start position. 
5) Press the module start button.
6) If generator set assemble pre‐heater (air intake or
water  pre‐heater).  The  Pre‐heat  engine  will
illuminate  on  module  LCD.  Preheating  time  varies
by  coolant  temperature.  Usually  water  pre‐heater
completes  in  about  60  seconds,  air  intake
pre‐heater completes 10 seconds. After preheating
the LCD puts out and the engine begins to start. It
will attempt to start again about 5 seconds later if
the engine fails to start.
7) After  the  engine  starts  successfully,  allow  the
engine  to  warm  up  for  about  5  minutes.  If  the
engine could not fire during the pre‐set number of
attempts to start (start attempts number: 3 times),
the  Alarm  LCD  would  flash.  If  you  need  to  restart,
wait at least 30 seconds before the retry.
8) Check the reading of Voltage Meter and Frequency
Meter  by  operating  the  Voltmeter  Change‐Over
Switch.  Once  the  generator  set  is  running  at  the
correct voltage and frequency, Turn the Generator
set main circuit breaker to  "ON".
9) Turn  on  every  switch  or  circuit  breaker  of  loads
(from heavy to light load in sequence), send power
to the load side.
Control panel introduction 
NO            Model     
1   
  start panel power switch 
2   
  battery charger switch 
3   
  fuse 
4   
  battery charger 
5   
  control module 
6   
  electric governor 
3.6.2 
Generating set control system 
To  control  and  monitor  the  generating  set,  an 
electronic  control  system  has  been  used.  P10/16 
model  control  system  is  fitted  from  10  kVA  to  2000 
KVA  single  generator  set  running  system.  P20/25 
control  system  is  fitted  from  10  kVA  to  2000  kVA 
transfer  with  mains  power.  Control  panel  provides  a 
means  of  starting  and  stopping  the  generating  set, 
monitoring 
its 
automatically  shutting  down  the  set  in  the  event  of 
critical  condition  arising  such  as  low  oil  pressure  or 
high engine temperature.(DSE Control system please 
read the DSE user's manual) 
P20/25 control system module introduction 
Main function of P20/25 
The  control  system  of  diesel  generator  set  is 
developed  through  the  use  of  model  AMF20/25 
module,  a  special  diesel  controller,  made  by  Czech 
COMAP  Company.  This  module  is  mainly  used  for 
auto/manual 
start‐up, 
manual/auto switchover the generator set power and 
mains 
power. 
14
User manual
operation 
and 
output 
protective 
stop 
It 
can 
also 
and 
and 
remote 

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents