Under  normal  conditions,  the  air  volume  generated 
from  the  radiator's  fan  is  enough  to  meet  the 
requirement of the working room ventilation.   
The air inlet temperature of the engine shall be below 
30  degree  Celsius.  If  the  air  inlet  temperature  keep 
rising  above  30  degree  Celsius,  the  engine's  output 
power  will  be  reduced,  and  therefore  fresh  air  from 
outside  shall  be  introduced  into  the  generator  set's 
working room in a timely manner. 
If  the  generator  set  is  furnished  with  a  remote 
radiator,  forced  air  circulation  for  the  generator  set 
working  room  is  a  must.  The  forced  air  circulation 
need  two  fans,  one  fan  is  responsible  for  air  intake, 
another  is  air  exhaust,  which  exhausts  hot  air  to 
outside. 
When the engine is furnished with propelled fan, it is 
recommended  that  a  separate  pipe  is  needed  to 
exhaust the gas which generated from the crankcase 
to  outside.  Otherwise  the  exhaust  gas  from  the 
crankcase will accumulate on the radiator, which will 
cause  the  radiator  stuck  by  dirty  material,  and  as  a 
result, the heat‐sinking capacity will be reduced. 
2.5.3 
Exhaust 
Our  standard  configuration  diesel  generator  sets 
provide  accessories  such  as  industry  heavy  silencer, 
soft corrugated pipe and elbow etc. Users can design 
the  exhaust  system  of  generator  set  working  room 
by  themselves.  When  design  and  install  the  exhaust 
system, please consider the following aspects: 
◆Ensure the total exhaust backpressure no higher than 
the  maximum  allowed  value  specified  by  the 
engine(usually  generator  set's  maximum  exhaust 
backpressure  is  no  more  than  5Kpa)  Fix  the  exhaust 
system  to  make  sure  the  exhaust  manifold  and 
turbo‐charger are not subject to the vertical pressure 
and side stress. 
◆ Reserve  some  space  for  hot  shrinkage  and  cold 
expansion. 
◆Reserve space for generator set vibration. 
◆Reduce exhaust noise level. 
Overload  of  exhaust  backpressure  will  cause 
following adverse effect: 
◆Output power loss 
◆Fuel efficiency reduce 
◆Exhaust gas temperature rise 
Note: 
When  more  than  one  generator  set  are  installed,  try 
not  to  discharge  all  of  the  generator  sets'  gas  from 
one  exhaust  path.  If  no  separated  exhaust  pipe  is 
allowed,  under  the  condition  that  the  total 
backpressure will not exceed the generator sets' total 
backpressure  a  moveable  separate  panel  shall  be 
installed  inside  of  the  branch  exhaust  pipe  so  that  to 
prevent the gas from return. 
In  the  exhaust  system,  soft  corrugated  pipe  shall  be 
used  to  connect  the  exhaust  pipe  with  the 
turbocharger,  this  pipe  has  three  functions  as 
follows: 
◆Separate  the  diesel  engine  with  vibration  and  the 
weight of exhaust pipe. 
◆Compensate the heat expansion of exhaust pipe. 
If  the  diesel  generator  set  is  installed  on  the 
anti‐vibration  base  frame,  the  corrugated  pipe  can 
compensate sideway movement when engine start or 
stop. 
Note: 
1. Serious  damage  will  occur  when  rain or  condensed
water  enter  into  engine's  exhaust  system. 
Therefore,  one  water  discharge  opening  shall  be 
installed  in  the  long  exhaust  pipe,  the  position  of 
which shall be close to the generator set.   
2. When  the  top  of  the  exhaust  pipe  is  above  the
architecture,  lightening  protection  is  needed 
(connect to the ground) 
2.5.4
 Noise reduction
When diesel generator set is running, normally it will 
generate noise level of 90~110dB, and the more the 
load, the higher the noise level.   
In order to meet the noise level standards established 
by the local environmental protection bureau and to 
prevent  the  noise  pollution  caused  to  ambient 
environment,  which  will  affect  people's  normal  life, 
to  reduce  noise  level  of  diesel  generator  set  is  also 