Led Display Indicators - Graco BDS Instructions-Parts List Manual

Batch dispense system proportioning controller
Table of Contents

Advertisement

Voltage Input Selector
Header (factory set for
120 or 220 VAC power)
1/4 Amp Input Fuse
Rapid Exchanger
Solenoid Valve
(RESV) Relay
RESV Factory
Wiring Terminal
Figure 11 – 120/220 VAC Electrical Power Control Unit Power Module
WARNING
FIRE AND EXPLOSION HAZARD
The controller is designed for use in a
non-hazardous location as defined in the
National Electrical Code (USA). To install
the Batch Dispense equipment in a
Class 1, Division 1, Group C and D
environment, the X-purge option must be
properly installed.
X-Purge Option
Isolated Coil Voltage
Transformer
20 Amp Enclosure
Power Fuse
Power Control Switch
Cable Header
Power Module
Wiring Terminal

LED Display Indicators

Power Off: Enclosure Power Relays De-energized
Power On: Enclosure Power Relays Energized
Safe Pressure: Enclosure Pressure > 0.15" or
0.50" w.c.
Rapid Exchange: Enclosure Pressure > 2.0" w.c.
Timer Running: Rapid Exchanger Timer Activity
Alarm Activity: Enclosure Pressure < 0.15" w.c.
Bypass Engaged: Control Bypass Active – Condi-
tional Bypass and Unconditional Bypass Modes
Latch Engaged: Power Relay Latch Active – Power
Latching Mode
Voltage Regulators
Pressure Switch
Cable Header
Logic Module
Cable Header
Redundant Safe
Pressure Relay
Redundant Rapid
Exchange Relay
20 Amp Alarm Relay
20 Amp Enclosure
Power Relays
309279