Configure Inverter Settings
Adjusting Inverter Settings
1. See
Table
6-1. Navigate to the inverter device
page using the right arrow key (next page right of
the home screen).
2. Push the center button.
3. Select Mod. Settings using the down arrow to scroll
and the center button to select.
Setpoint
PLM_Channel
TargMaxImprtP
-30,000 to +30,000 Watts
TargMinImprtP
-30,000 to +30,000 Watts
EnaIslanding
NumTranSwtchs
ExtTransVolt
80 – 140 Volts
ExportOverride
CalOverride
CTTurnsRatio
1,500 – 3,000 Turns
EnaLoadShed
GridParInvrtrs
ACPVPower
0 – 7.6 kW
GenPower
0 – 24 kW
GenCtrlMode
Installation and Owner's Manual for Generac PWRCell Inverter
Table 6-1. Inverter Settings
Range
Default
0 – 12
1
Maximum Threshold for importing power before the battery will discharge in
0
0
Allows system to go into island mode, providing backup power during a util-
on / off
on
0 / 1 / 2
0
95
on / off
off
Overrides inverter logic for automatic detection of included Generac current
on / off
off
1,500
0 / 1 / 2
0
This setting allows for two inverters to share one set of CTs. Set to 2 if daisy
1 – 2
1
0
0
0 / 1 / 2
0
4. Scroll through the settings using the up / down
arrow keys.
5. Use the center button to select a setting.
6. Use the up / down arrow keys to change the value
of a setting.
7. Use the center button to deselect a setting.
8. Scroll down and save all changes before exiting
the Mod. Settings menu.
9. Select Mod. Settings again to verify changes were
saved.
Channel for REbus communications. All devices in a system must use the
same channel (except REbus Beacon). Do not set equipment to channel 0
Commissioning Multiple Inverter Systems
unless performing
Self Supply Mode to offset.
Minimum power import maintained by charging the battery from the grid in
ity service interruption. Turn this setting off for PV only installations.
Defines the number of external automatic transfer switches installed and
enables transfer switch controls.
For AC Coupled PV, this must be 1.
Minimum voltage from the utility that must be present for the inverter to
reconnect back to the grid. If an ATS is installed, this will be the voltage
required for the inverter to control the ATS back to the normal (utility) posi-
Formerly called Zero Export, this setting will inhibit the PWRcell system
from exporting power to the grid. This setting is for temporary use and will
not satisfy CRD200 Import Only Compliance. See
Allows a different turns ratio to be set for specific CTs.
Select 1 if using SMM devices to shed loads. Select 2 if using the PWRcell
ATS Controller to shed loads (with or without SMMs).
chaining CTs between two inverters.
Power rating of the attached AC coupled PV array. If no AC coupled PV
array is attached leave at 0.
Set this value to the cumulative power rating of all AC coupled PV systems
connected to this inverter. This value must not exceed 7.6 kW. An incorrect
higher value will result in insufficient charging of the batteries, an incorrect
lower value will result in the possibility of an over-voltage event.
Reserved for future functionality.
Reserved for future functionality.
Description
Self Supply Mode.
tion.
Set Export Override
(optional)
.
transformers (CTs).
Commissioning
.
31