Commissioning

Test Island Mode

To test Island Mode, AC power to the inverter must be
disconnected. If configured to provide backup power to a
protected loads subpanel, this may be accomplished by
turning OFF the solar backfeed breaker or solar AC dis-
connect. If configured to operate with a PWRcell ATS, AC
power must be disconnected to the inverter and the ATS
to testing islanding.
– Ensure inverter setting "EnaIslanding" is set to
'on.'
– Ensure Protected Loads breaker at the inverter
Power Core is in the ON position.
– Ensure system is set to an appropriate system
mode (e.g., Clean Backup, Priority Backup, Self
Supply).
NOTE: Exact electrical system configurations will vary. It
is up to the operator to perform this test accurately for the
configuration onsite.
NOTE: Per UL 1741, the PWRcell Inverter may require
five minutes upon recovery from a grid outage or island-
ing event before exporting power.

Configure Time of Use (optional)

REbus Beacon allows the PWRcell system to manage
energy production and storage over the course of the
day. This is called Time of Use (TOU) energy manage-
ment. To take advantage of this functionality, the PWRcell
system must include a PWRcell Battery and a reliable
connection to the Internet via an Ethernet connection to a
router.
NOTE: Enable and setup the REbus Beacon for TOU
scheduling only. Otherwise, do not enable the REbus
Beacon.

Configuring and Running a TOU Schedule

1. See
6-11. Navigate to the Beacon device
Figure
page and press the center button to enter the
device menu.
REbus Beacon
TOU Scheduler
disabled
To enable scheduler,
press center button
and select "Enable".
Figure 6-11. Configuring TOU Schedule (1 of 4)
34
2. See
Figure
highlight Mod. Settings and press the center button
to enter the settings menu.
REbus Beacon
Enable
Mod. Settings
Remove Device
RCPn: 00010012XXXX
< EXIT
Figure 6-12. Configuring TOU Schedule (2 of 4)
3. See
Figure
highlight Access Code and press the center button
to select.
4. Use the up and down arrows to set the Access
Code to 57, and press the center button.
NOTE: The access code is valid for five minutes. After
five minutes, the access code must be entered again to
enable changes.
Access Code:
TOU Schedule:
Time Zone:
Cancel
Figure 6-13. Configuring TOU Schedule (3 of 4)
5. Use the up and down arrows to highlight TOU
Schedule and press the center button to select.
6. Use the up and down arrows to adjust the TOU
Schedule code. Once the desired value is set,
press the center button to exit edit mode.
NOTE: See the latest Time of Use Program Guide for
current TOU schedule values. The program guide is
https://www.generac.com/resources-and-
available at
tools/ce-installer-resources/installation-resources.
7. Set the Time Zone to the desired location based on
Table 6-3: Time Zone
value is set, press the center button to exit edit
mode.
010109
Installation and Owner's Manual for Generac PWRCell Inverter
6-12. Use the up and down arrows to
SCROLL > NEXT • SELECT
6-13. Use the up and down arrows to
Save
Codes. Once the desired
Menu
012452
57
1