Location and Compliance
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and shall not be aggregated above 30 kW on a single point of com-
mon coupling.
All PWRcell Inverters are shipped from the factory in compliance with all UL 1741 requirements, including IEEE 1547.
If permission to operate (PTO) is dependent on compliance to a specific utility standard, follow the steps covered in the
Set Inverter Grid Compliance (optional)
Voltage Trip Thresholds
See
Table 3-3
for the default fixed voltage trip setpoints. All over voltage and under voltage trip conditions result in a
300-second restart delay time after the trip threshold has been exceeded for the listed number of cycles.
The inverter is disconnected from the grid during this 300-second delay.
Frequency Trip Thresholds
See
Table 3-3
for the default fixed frequency trip setpoints. All over frequency and under frequency trip conditions
result in a 300-second restart delay time after the trip threshold has been exceeded for the listed number of cycles.
The inverter is disconnected from the grid during this 300-second delay.
Voltage Trip Thresholds
Threshold
(% of nominal)
OV4
OV3
OV2
OV1
UV1
UV2
UV3
UV4
*Value of 999 indicates a disabled threshold for voltage trips.
**Value of zero indicates a disabled threshold for frequency trips.
12
section in this manual.
Table 3-3. Voltage Trip and Frequency Thresholds
Threshold
No. of Cycles
999*
1
130
1
120
10
110
60
88
120
50
10
999*
1
999*
1
Frequency Trip Thresholds
Threshold
Threshold
(% of nominal)
OF4
OF3
OF2
OF1
UF1
UF2
UF3
UF4
Installation and Owner's Manual for Generac PWRcell Inverter
No. of Cycles
0**
1
0**
1
0**
1
0.5
10
0.7
10
0**
1
0**
1
0**
1