Confirm Inverter Settings; Pv Only System; Pv + Battery W / A Protected Loads Panel For Partial Home Backup - Generac Power Systems PWRcell XVT076A03 Installation And Owner's Manual

Hide thumbs Also See for PWRcell XVT076A03:
Table of Contents

Advertisement

System Operation
PV Link S2502
Enable
Enable
Mod. Settings
Enable w/PVRSS
Cancel
RCPn: 00010003XXXX
< EXIT
SCROLL > NEXT • SELECT
Figure 7-12. Enabling REbus Devices (3 of 3)
a. Notice there will be multiple pages of S2502 PV
Links. Watch the horizontal cursor at the top of each
page to indicate a new page. Press the center but-
ton on a device to reference its RCPn and confirm
the device ID.
11. See
Figure
7-13. Confirm PV Links are in state,
"making power."
a. See
Figure
7-14. If the PV Link goes directly to
"low sun," disable the device and select "Enable
w/PVRSS."
b. If the PV Link still goes directly to "low sun,"
contact the Independent Authorized Service
Dealer (IASD) who installed the system.
PV Link S2502
Photovoltaics
Making Power
Power:
PV Voltage:
E-total:
Figure 7-13. PV Link Device Page
PV Link S2502
Disable
Mod.
Settings
Enable w/PVRSS
RCPn: 00010003XXXX
< EXIT
SCROLL > NEXT • SELECT
Figure 7-14. PV Link - Enable w/PVRSS
12. Confirm PWRcell Batteries are in state "standby,"
"charging," or "discharging" (state will depend on
system mode selected).
46
Menu
Save
013440
-xx
0W
115v
59.0kWh
013439
Menu
013437
NOTE: It is only necessary to enable the REbus Beacon
if setting the system to operate on a Time of Use (TOU)
schedule. See
Section 6:
Time of Use (optional)

Confirm Inverter Settings

Once the system is activated, confirm the system mode,
and navigate to the inverter device page. Press the cen-
ter button to access the "Mod. Settings" menu for the
inverter, and confirm the settings are set correctly for the
system installed.

PV Only System

– System mode should be "Grid Tie."
– See
Figure 7-15
Settings:"
o 'EnaIslanding' should be 'off.'
o All other settings should be at their default
values.
PWRcell 2P Inv.
Disable
Mod. Settings
Calibrate CTs
RCPn: 000100073212
< EXIT
SCROLL > NEXT • SELECT
Figure 7-15. PV Only System (1 of 2)
TargMinImprtP
Enalslanding
NumTranSwtchs
ExTransVolt
Cancel
Figure 7-16. PV Only System (2 of 2)
PV + Battery w / a Protected Loads Panel for
Partial Home Backup
– System mode should be Self Supply, Clean
Backup, or Priority Backup.
– See
Figure 7-17
Settings:"
o 'EnaIslanding' should be 'on.'
o All other settings should be at their default
values.
Installation and Owner's Manual for Generac PWRCell Inverter
Commissioning Configure
for more information.
and
Figure
7-16. Inverter "Mod.
Menu
013436
off
95
Save
and
7-18. Inverter "Mod.
Figure
0
0
013438