– CT1 must be connected to Line 1.
– CT2 must be connected to Line 2.
– CT3 must be connected to line 3 (for three phase
applications).
Setpoint
Behavior
Overrides CT calibration.
When set to OFF, the inverter will automatically detect the direction and
CalOverride
number of CTs present.
When set to ON, the inverter will assume correct CT installation and will
use the readings as is.
Turns ratio of the CTs installed.
Default turns ratio of 1,500 is compatible with included clamp type CTs
CTTurnsRatio
If installation restriction requires larger accessory CTs, set point shall be
adjusted to 3,000. Verify turns ratio of CTs before modifying this setting.
Allows two inverters to share one set of CTs.
GridParInvrtrs
If set to "1" only one inverter should be using a single set of CTs.
If set to "2" two inverters can share one set of CTs.
Event Name
ct cal = 1
ct cal = 2
ct cal = 3
ct cal = 4
ct cal = 5
ct cal = 6
ct cal = 7
ct cal = 9
ct cal = A
ct cal = B
ct cal = C
ct cal = D
ct cal = E
ct cal = F
ct cal success
Installation and Owner's Manual for Generac PWRCell Inverter
Table 5-11. CT Setpoints
Table 5-12. Automatic Detection Troubleshooting Table
Event Code
Description
0x8061
Line 1 doesn't have a valid CT calibration
0x8062
Line 2 doesn't have a valid CT calibration
0x8063
Line 1 & 2 don't have a valid CT calibration
0x8064
Line 3 doesn't have a valid CT calibration
0x8065
Line 1 & 3 don't have a valid CT calibration
0x8066
Line 2 & 3 don't have a valid CT calibration
0x8067
Line 1 & 2 & 3 don't have a valid CT calibration
0x8069
Line 1 has multiple CTs on it (or a CT is on the neutral wire)
0x806A
Line 2 has multiple CTs on it (or a CT is on the neutral wire)
0x806B
Lines 1 and 2 have multiple or missing CTs on them (or a CT is on the neutral wire)
0x806C
Line 3 has multiple CTs on it (or a CT is on the neutral wire)
0x806D
Lines 1 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire)
0x806E
Lines 2 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire)
0x806F
Lines 1 & 2 & 3 have multiple or missing CTs on them (or a CT is on the neutral wire)
0x8070
Calibration was successful
– All CTs must be orientated in the same relative
direction.
– In certain scenarios, additional setpoint modifi-
cations may need to be made. See
CT Setpoints
for more information.
Electrical Connections
Table 5-11:
Default
Units
OFF
N/A
1,500
Turns
1
N / A
27