Location and Compliance
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and
shall not be aggregated above 30 kW on a single point of
common connection.
All PWRcell inverters are shipped from the factory in
compliance with all UL1741 requirements, including
IEEE1547. If permission to operate (PTO) is dependent
on compliance to a specific utility standard, follow the
steps covered in
Installer Configuration Tool
this manual.
Voltage Trip Thresholds
Threshold
(% of nominal)
OV1
OV2
OV3
OV4
UV1
UV2
UV3
UV4
*Value of 999 indicates a disabled threshold for voltage trips
**Value of zero indicates a disabled threshold for frequency trips
10
section in
Table 3-2. Voltage Trip and Frequency Thresholds
Threshold
No. of Cycles
110
120
120
10
130
1
999*
1
88
120
50
10
999*
1
999*
1
Voltage Trip Thresholds
See
Table 3-2
for the default fixed voltage trip setpoints.
All over voltage and under voltage trip conditions result in
a 300-second restart delay time after the trip threshold
has been exceeded for the listed number of cycles.
Frequency Trip Thresholds
See
Table 3-2
for the default fixed frequency trip set-
points. All over frequency and under frequency trip condi-
tions result in a 300-second restart delay time after the
trip threshold has been exceeded for the listed number of
cycles.
Frequency Trip Thresholds
Hz Over/
Threshold
Under Nominal
OF1
OF2
OF3
OF4
UF1
UF2
UF3
UF4
Installation Manual for Generac PWRcell Inverter
No. of Cycles
0.5
120
2
6
1.3
0
0**
1
0.5
120
2
10
0**
1
0**
1
Need help?
Do you have a question about the PWRcell XVT076A03 and is the answer not in the manual?
Questions and answers