Technical Data - Samson TROVIS 5757-7 Mounting And Operating Instructions

Electric actuator with process controller for heating and cooling applications
Table of Contents

Advertisement

3.2 Technical data

TROVIS 5757-7
Connection to valve
Rated travel
Transit time for rated travel
Thrust
Supply voltage
Power consumption
Temperature sensor
Operating temperature range
Binary inputs
BI1
(instead of the
 1)
potentiometer)
BI2
(instead of return flow
1)
sensor)
Potentiometer input
Switching output
Permissible temperature ranges
Ambient
Storage
Degree of protection
Class of protection
Device safety
Noise immunity
Noise emission
Conformity
Weight
Recommendation: use devices with gold contacts when using relays.
1)
The permissible medium temperature depends on the valve on which the electric actuator with
2)
process controller is mounted. The limits in the valve documentation apply.
EB 5757-7 EN
Force-locking
6 mm
20 s
300 N
230 V (±10 %)/50 Hz
5 VA
max. 3x Pt 1000
–40 to +150 °C
Floating contact, contact load 5 V/1 mA
Floating contact, contact load 5 V/1 mA
1000 to 1100 Ω or 1000 to 2000 Ω
230 V/50 Hz/1 A; circulation pump or demand for externally
required signal
 2)
0 to 50 °C
–20 to +70 °C
IP 42 according to EN 60529
II according to EN 61140
According to EN 61010-1
According to EN 61000-6-2 and EN 61326-1
According to EN 61000-6-3 and EN 61326-1
·
Approx. 0.7 kg
Design and principle of operation