Samson TROVIS 5757-7 Mounting And Operating Instructions page 58

Electric actuator with process controller for heating and cooling applications
Table of Contents

Advertisement

Annex
Parameter list
There are separate two parameter levels #1 and #2. Both parameter levels contain the
functions P01 to P23 with the specified default settings and setting ranges.
The parameters have the setting ranges as listed below.
P
Parameter
01
Flow temperature set point
02
Flow temperature set-back in reduced operation
03
Min. flow temperature
04
Max. flow temperature
05
Heating characteristic gradient
06
Heating characteristic level
07
Gradient shift range via potentiometer
08
Level shift range via potentiometer
09
Kp flow temperature control
10
Tn flow temperature control
11
Ty actuator transit time for valve travel
12
Dead band (switching range)
13
Max. return flow temperature
14
Kp return flow temperature limitation
15
Tn return flow temperature limitation
16
Delay time for outdoor temperature
17
Outdoor temperature limit value at rated operation
18
Outdoor temperature limit value at reduced operation
19
Room temperature set point at rated operation
20
Room temperature set point at reduced operation
21
Max. room temperature boost for switch-off
22
Time interval for flash adaptation
23
Pump lag time
16-4
Default
Adjustment range
70 °C
0 to 150 °C
15 K
0 to 50 K
20 °C
0 to 150 °C
120 °C
0 to 150 °C
1.6
0.2 to 3.2
0 K
–30 to +30 K
1.0
0.0 to 1.5
15 K
0 to 30 K
2.0
0.1 to 50.0
120 s
0 to 999 s
24 s
10 to 240 s
2.0 %
0.5 to 5.0 %
50 °C
10 to 90 °C
1.0
0.1 to 50.0
400 s
0 to 999 s
3.0 °C/h
1.0 to 6.0 °C/h
22 °C
0 to 50 °C
15 °C
0 to 50 °C
20 °C
10 to 40 °C
15 °C
10 to 40 °C
2 K
1 to 6 K
10 min
0 to 100 min
5 min
1 to 999 min
EB 5757-7 EN