Probe Length; Tank Capacity; Volume Offset - Omntec OEL8000II Installation Manual

Hide thumbs Also See for OEL8000II:
Table of Contents

Advertisement

Programming
4.3.4.19
The probe length is the length of the magnetostrictive probe's shaft in inches.
1. Enter the probe length (see Section 2.3.1 – MTG Probe Length). You may enter
2. Select ENTER.
4.3.4.20
1. Enter the volume tank capacity in gallons (maximum of 10 numerical characters).
2. Select ENTER.
4.3.4.21
Volume Offset is a calibration to compensate for consistent discrepancies that may be
found between actual and displayed volume.
When initially programming the controller, leave the default value of zero (0).
1. Enter the volume offset in gallons (maximum of 10 numerical characters).
4-24
System Response
Lines 1 and 4 of Figure 4-7c remain unchanged.
Line 2 reads: Set the probe length for the tank, (In).
Line 3 shows a cursor.

Probe Length

up to10 numerical characters.
System Response
The probe length will appear on line 3.
System Response
Lines 1 and 4 of Figure 4-7c remain unchanged.
Line 2 reads: Set the tank capacity, (G).
Line 3 shows a cursor.

Tank Capacity

System Response
The tank capacity will appear on line 3.
System Response
Lines 1 and 4 of Figure 4-7c remain unchanged.
Line 2 reads: Set a vol. offset (G).
Line 3 shows a cursor.

Volume Offset

Important!
®
OMNTEC
Mfg., Inc.