50
Error
A B
C
Error
code
16 R
2
E16
Firmware 2.9 and
up:
FPC fault (option)
Only active if the
"Fire Protection
Controller" acces-
sory is connected
to the unit.
No communica-
tion with the
fire protection
controller
There is no posi-
tion feedback for
fire dampers
Error in monthly,
weekly or manual
test of fire damp-
ers
INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Possible cause
Fire protection
controller with
this address has
previously been
installed but can
no longer be
reached
A fire damper
is closed, but
should be open
Fire damper stuck
in either open or
closed position
Maintenance and care: Error list
Action
Reset
required
Check connection
Perform a
to fire protection
manual reset
controller
by pressing the
alarm button on
the control panel
or by turning the
unit off/on
Check power supply
to fire dampers
Check fire dampers
internal fire detector
The fire damper is
blocked.
Fire dampers are con-
nected incorrectly
Fire damper defec-
tive