Error List - Dantherm RCV 320 P2 Basic Manual

Hide thumbs Also See for RCV 320 P2 Basic:
Table of Contents

Advertisement

INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Maintenance and care: Error list

Error list

See the list below for a complete description:
A B
-
1
2
Error
C
Error
code
Y
1
-
Filter alarm
R
1
E 1
Extract air fan
No feedback
about rotational
speed (tacho)
from extract air
fan
Extract air fan un-
able to operate at
the desired speed
R
1
E 2
Supply air fan
No feedback
about rotational
speed (tacho)
from supply air
fan
Supply air fan
unable to run at
desired speed
Action
Possible cause
required
Filter period
Dismount filters and
expired
inspect for dirt
Replace filters and
reset alarm
The filters are
Extend the filter
not soiled, so the
timer period
filter period is too
short
The filters are
Replace filters and
soiled
reset alarm
Filters are
Replace filters and
clogged, filter
reset alarm
period is too long
Shorten the filter
timer period
Extract fan power
Connect the power
cable not con-
cable to the extract
nected
air fan
Extract air fan
Connect control ca-
control cable not
ble to extract air fan
connected
Extract air fan not
Replace extract air
working
fan
Fan speed set-
Decrease fan speed
point too high
setpoint
Fan defective
Replace fan
Power cable to
Connect the power
supply air fan not
cable to the supply
connected
air fan
Supply air fan
Connect the supply
control cable not
air fan control cable
connected
Supply air fan not
Replace supply air
working
fan
Fan speed set-
Decrease fan speed
point too high
setpoint
Fan defective
Replace fan
Reset
Reset alarm and
reset filter by
pressing and
holding alarm
button for 5
seconds
Press and hold
the centre
button on the
wireless remote
control for 10
seconds
The same proce-
dure can be used
to reset the filter
before the alarm
is triggered.
Perform a
manual reset
by pressing the
alarm button on
the control panel
or by turning the
unit off/on
Automatic
reset after 140
seconds, but the
alarm reappears
if the problem is
still present
Perform a
manual reset
by pressing the
alarm button on
the control panel
or by turning the
unit off/on
Automatic reset
after 140 sec-
onds, but alarm
reappears if
problem persists
45