INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Installation: Mounting the device
Drain/condensate
The unit is equipped with a blanked-off drain. Connect the drain hose to the correct conden-
drain
sate outlet at the bottom of the unit.
Step Action
1
2
!
3
!
4
Check the ventilation system's
mode (A/B) on the main PCB.
(see also "Accessing the main PCB"
on page 25)
Make sure that the plug is fitted in
the unused condensate outlet.
Note: Otherwise, condensation
water cannot be drained from the
unit and this will result in an in-
advisable accumulation of water
in the unit with the risk of water
entering the house!
Connect the drain hose to the
drain outlet in use and secure
the connection with the supplied
hose clamp.
Note: Never use a metal clamp,
which you have to tighten with a
screwdriver.
The drain hose must be fitted
with one of the illustrated siphons
of min. 100 mm.
Illustration
Mode B
Mode A
Drain outlet in use (open)
B
A
The CLOSED
drain outlet (plug
must be fitted)
35