Maintenance and care: Error list
A B
13 -
14 R
15 R
Error
C
Error
code
0
E 13
Communication
error / poor signal
Shown only on
wireless remote
control
No wireless signal The ventilation
Wireless signal is
too weak
2
E 14
Fire alarm
Duct-connected
fire thermostat
(accessory)
Input is normally
closed (NC) but is
now open
1
E 15
High water level
sensor (accessory)
Water level too
high
The water level is
not too high
Action
Possible cause
required
Turn on the ventila-
unit is switched
tion system
off
Antenna not
Install antenna
mounted on unit
The remote con-
Move it closer to the
trol is too far from
ventilation system
the ventilation
Install antenna exten-
system
sion cable
Fire or smoke
Check for smoke or
sensor connected
fire
to this input is
active
Check if sensor and
connection are OK
Nothing connect-
Install short circuit
ed to this input
accessory
Water outlet is
Clean the water
clogged
outlet
The water outlet
Check that the water
is installed incor-
outlet is mounted on
rectly
the correct side and
that the pipes are not
above the drain level.
Auxiliary drain
Check the pump
pump not run-
ning.
Inspect fuse
Water level sensor
Check wiring
disconnected
Water level sensor
Configure or replace
normally open
the water level sen-
(NO)
sor so it is normally
closed (NC).
Digital input
Check the configura-
configured incor-
tion of the digital
rectly
input using PC Tool
Reset
Try again every
5 minutes or
if a button is
pressed
The alarm dis-
play can be reset
by pressing the
alarm button or
by turning the
unit off/on.
However, the
unit cannot be
started until the
alarm conditions
have disap-
peared
Automatic reset
when input is
closed again
49