The siphon can be made in two
ways:
A) just below the unit (suitable
for the majority of wall
installations) or alternatively
B.
at the end of the drain
hose (suitable for floor
installations)
Make also sure that you:
route the hose to a drain and
ensure that it is not exposed
to frost.
fill the siphon with min. 0.5 L
water.
let the drain hose drop with
1% (1 cm/ meter) all the way
from the unit to the drain.
Optional use of clamp:
5
If you make the siphon just below
the unit, you may like to use the
cable clamp included in delivery.
Mount the cable clamp in the
hole in the bottom of the unit
Pass the drain hose through
the cable clamp to form a
siphon.
Material damage (e .g . water damage)
Heat recovery of air with a high moisture content leads to condensation in the heat ex-
changer. Condensate must be led into a drain, as it otherwise may damage the floor under
the unit.
Make sure that the drain hose is installed according to the current operating mode.
Material damage (e .g . water damage)
Frozen water in the hose can damage the drain hose, thus causing a water damage at the
installation site.
Insulate the drain hose completely, where it is exposed to low temperatures, in order to
ensure that the installation always is frost-proof.
If the insulation can't be done in a way that ensures a frost-proof drain hose, we recom-
mend to connect a heating cable around the drain hose.