KEB COMBIVERT H6 Series Instructions For Use Manual page 53

Installation rectifier module
Hide thumbs Also See for COMBIVERT H6 Series:
Table of Contents

Advertisement

CERTIFICATION
Inverter
Inverter
Copper conductors
19H6
20H6
60°C or 75°C
21H6
24H6
25H6
75°C
27H6
28H6
These supply modules are only for use with drive modules that are part of the
COMBIVERT H6 series.
Brake Resistors provided in the end-use shall be controlled by manufacturer and
type designation, and separately subjected to above specified tests, due to differ-
ences in brake resistors construction, even with identical rating.
Connection of an External Temperature Sensor was not evaluated.
Maximum heatsink temperature for H6 models shall be maintained at the following
listed values via a liquid cooled system:
Maximum heatsink
temperature
19H6
80°C
20H6
21H6
60°C
24H6
80°C
25H6
60°C
27H6
80°C
28H6
60°C
Suitable for use on a Circuit Capable of delivering not more 18k rms Symmetrical
Amperes, 480 Volts maximum when protected by fuses as specified in the follow-
ing table: