Table 19: Emc - Immunity To Interference - WAGO 750-439/040-000 Manual

8-channel digital input; namur; intrinsically safe; extreme for wago i/o system 750 xtr
Table of Contents

Advertisement

30
Device Description
Pos: 18.37 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung (alte Struktur)/Normen und Richtlinien/EMV-Normen I/O-Modul 750-xxxx/0040-0000, nur Standardversion - Einleitung XTR @ 18\mod_1395909426189_21.docx @ 149708 @ @ 1
The I/O module 750-439/040-000 meets the following EMC standards as these
standards relate to the I/O module:
Pos: 18.38 /Serie 750 (WAGO-I/O-SYSTEM)/Gerätebeschreibung (alte Struktur)/Normen und Richtlinien/Normen Störfestigkeit XTR (Ex i Sonderfall -439) @ 31\mod_1515493438385_21.docx @ 473119 @ @ 1
Table 19: EMC – Immunity to Interference
Standard
Electrostatic Discharge
• EN 61000-4-2
• EN 60255-26
• IEEE C37.90.3
High-frequency Electromagnetic Fields
• EN 61000-4-3
• EN 60255-26
• IEEE C37.90.2
Fast Electrical Transient Disturbances / Burst
• EN 61000-4-4
• EN 60255-26
• IEEE C37.90.1
Surge Voltage / Surge
• EN 61000-4-5
• EN 60255-26
Conducted Disturbances, Induced by High-frequency Fields
• EN 61000-4-6
• EN 60255-26
Magnetic Fields With Electrical Frequencies
• EN 61000-4-8
• EN 60255-26
Damped Oscillatory Magnetic Fields
• EN 61000-4-10
Voltage Dips, Short-term Interruptions and Voltage Fluctuations
• EN 61000-4-11
• EN 60255-26
Damped Sinusoidal Oscillations
• EN 61000-4-12
Harmonics and Interharmonics
• EN 61000-4-13
Conducted Asymmetric Disturbances
• EN 61000-4-16
Manual
Version 1.1.0
750-439/040-000 8DI NAMUR Ex i XTR
Test Value
8 kV (contact discharge)
8 kV (air discharge)
20 V/m (80 MHz ... 1 GHz)
10 V/m (1 GHz ... 3 GHz)
3 V/m (3 GHz ... 6 GHz)
4 kV
1)
1 kV (conductor/conductor)
2 kV (conductor/ground)
10 V (150 kHz ... 80 MHz)
300 A/m continuous / 1000 A/m for 1 s
100 A/m
Standard not applicable
1)
1 kV (conductor/conductor)
2 kV (conductor/ground)
Standard not applicable
30 V continuous
300 V for 1 s
(Shielded cables must be used at cable
lengths of 10 m or more.)
WAGO I/O SYSTEM 750 XTR

Advertisement

Table of Contents
loading

This manual is also suitable for:

8di namur ex i xtr

Table of Contents