Mounting; Mounting Sequence - WAGO 750-439/040-000 Manual

8-channel digital input; namur; intrinsically safe; extreme for wago i/o system 750 xtr
Table of Contents

Advertisement

36

Mounting

Pos: 24 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 1/Montieren - Überschrift 1 @ 3\mod_1225446744750_21.docx @ 24900 @ 1 @ 1
5
Mounting
Pos: 25.1 /Serie 750 (WAGO-I/O-SYSTEM)/Montieren/Demontieren/Montagereihenfolge Überschrift 2 und Einleitung @ 3\mod_1231770210031_21.docx @ 25992 @ 2 @ 1
5.1

Mounting Sequence

Fieldbus couplers, controllers and I/O modules of the WAGO I/O SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos: 25.2 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Vorsicht/Vorsicht: Verletzungsgefahr durch scharfkantige Messerkontakte! @ 6\mod_1256193279401_21.docx @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
Pos: 25.3 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Warnung/Warnung: Anforderungen an Luft- und Kriechstrecken (XTR Ex i) @ 36\mod_1579514444035_21.docx @ 572089 @ @ 1
Requirements for Clearances and Creepage Distances
For all sections of a node that contain I/O modules for Ex-i use, stricter require-
ments with regard to clearances and creepage distances apply.
Before such a node section, the respective Power supply 24 VDC Diagn
for Ex i XTR Modules (750-606/040-000) ensures the required distance.
After such a node section, 4 Distance Modules XTR (750-616/040-000)
must be used.
Exception: If the following section consists only of an End Module XTR
(750-600), no distance modules are required.
Pos: 25.4 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Achtung/Achtung: I/O-Module nur in vorgesehener Reihenfolge stecken! @ 6\mod_1256194177073_21.docx @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Pos: 25.5 /Serie 750 (WAGO-I/O-SYSTEM)/Wichtige Erläuterungen (alte Struktur)/Sicherheits- und sonstige Hinweise/Hinweis/Hinweis: Busabschluss XTR nicht vergessen! @ 15\mod_1368426836647_21.docx @ 119458 @ @ 1
Manual
Version 1.1.0
WAGO I/O SYSTEM 750 XTR
750-439/040-000 8DI NAMUR Ex i XTR

Advertisement

Table of Contents
loading

This manual is also suitable for:

8di namur ex i xtr

Table of Contents