Mounting; Mounting Sequence - WAGO 750-407/040-000 Manual

2-channel digital input; 220 vdc; 3 ms; extreme for wago-i/o-system 750 xtr
Hide thumbs Also See for 750-407/040-000:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-407/040-000 2DI 220V DC 3.0ms XTR
Pos : 53 /All e Seri en (Allgemei ne Module)/Ü berschriften/Ebene 1/M onti eren - Ü bersc hrift 1 @ 3\mod_1225446744750_21.doc x @ 24900 @ 1 @ 1
5

Mounting

Pos : 54.1 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/M ontagerei henfolge Ü berschrift 2 und Einl eitung @ 3\mod_1231770210031_21.doc x @ 25992 @ 2 @ 1
5.1

Mounting Sequence

Fieldbus couplers, controllers and I/O modules of the WAGO-I/O-SYSTEM 750
are snapped directly on a carrier rail in accordance with the European standard
EN 60175 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual devices are securely seated
on the rail after installation.
Starting with the fieldbus coupler or controller, the I/O modules are mounted
adjacent to each other according to the project design. Errors in the design of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the I/O modules with power contacts (blade contacts) cannot be
linked to I/O modules with fewer power contacts.
Pos : 54.2 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und s onstige Hinweise/Vorsic ht/Vorsic ht: Verletz ungsgefahr durc h sc harfkantige M esser kontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1
Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury. Do not touch the blade contacts.
Pos : 54.3 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und s onstige Hinweise/Achtung/Ac htung: I/O-Module nur in vorgesehener R eihenfolge stec ken! @ 6\mod_1256194177073_21.doc x @ 43429 @ @ 1
Insert I/O modules only from the proper direction!
All I/O modules feature grooves for power jumper contacts on the right side. For
some I/O modules, the grooves are closed on the top. Therefore, I/O modules
featuring a power jumper contact on the left side cannot be snapped from the
top. This mechanical coding helps to avoid configuration errors, which may
destroy the I/O modules. Therefore, insert I/O modules only from the right and
from the top.
Pos : 54.4 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und s onstige Hinweise/Hinweis/Hi nweis : Bus absc hlus s XTR nic ht vergess en! @ 15\mod_1368426836647_21.doc x @ 119458 @ @ 1
Don't forget the bus end module!
Always plug a bus end module 750-600/040-000 onto the end of the fieldbus
node! You must always use this bus end module at all fieldbus nodes with the
WAGO-I/O-SYSTEM 750 XTR fieldbus couplers/controllers to guarantee proper
data transfer.
Pos : 54.5 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/I/O-Modul e 750xxxx/0040xxxx 4g-5g @ 15\mod_1367558844291_21.doc x @ 118470 @ @ 1
For vibration loads > 4g, observe the following installation instructions:
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
Make the open conductor length between strain relief and wire connection
as short as possible.
Use the reinforced end stop 249-197.
Pos : 54.6 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Mounting
33
Manual
Version 1.3.0

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

2di 220v dc 3.0ms xtr

Table of Contents