Rack Requirements

Step
5
6
7
8
9
Rack Requirements
The Oracle Exadata Storage Server X6-2 Extreme Flash is a 2 rack unit (2U) storage server that
fits inside Oracle's Exadata rack. The rack specifications are listed in the following table.
TABLE 6
Requirement
Usable rack units
Height
Width (with side panels)
Depth (front door handle to rear
door handle)
Weight
Maximum dynamic load
Structure
Rack horizontal opening and unit
vertical pitch
Distance between front and rear
mounting planes
Clearance depth in front of front
mounting plane
Clearance depth behind front
mounting plane
Clearance width between front
and rear mounting planes
Minimum clearance for service
access
20
Oracle Exadata Storage Server X6-2 Extreme Flash Installation Guide • July 2018
Description
Review safety precautions for rackmounting a
storage server.
Gather the tools and equipment necessary for
installation.
Ensure that all prerequisite tasks are complete
before installation.
Install the storage server into a rack.
Attach data and storage server management cables
to the storage server.
Exadata Rack Specifications
Specification
42
199.8 cm (78.6 inches)
60 cm (23.6 inches)
120 cm (47.24 inches)
150.6 kg (332 lbs)
1005 kg (2215 lbs)
Four-post rack (mounting at both front and rear). Supported rack types: square
hole (9.5 mm) and round hole (M6 or 1/4-20 threaded only).
Two-post racks are not compatible.
Conforms to ANSI/EIA 310-D-1992 or IEC 60927 standards.
Minimum 61 cm and maximum 91.5 cm (24 inches to 36 inches).
Distance to front cabinet door is at least 2.54 cm (1 inch).
Distance to rear cabinet door is at least 90 cm (35.43 inches) with the cable
management arm, or 80 cm (31.49 inches) without the cable management arm.
Distance between structural supports and cable troughs is at least 45.6 cm (18
inches).
Clearance, front of storage server: 123.2 cm (48.5 inches)
Links
"Safety Precautions When Rackmounting the
Storage Server" on page 26
"Tools and Equipment Needed for
Installation" on page 27
"Installation Prerequisites" on page 25
"Installing the Storage Server Into a
Rack" on page 25
"Cabling the Storage Server" on page 61