Maintenance Space Requirements; Configuration Restrictions; Exadata Database Machine X6-2 Configuration Restrictions - Oracle X6-2 Installation Manual

Exadata storage server extreme flash
Hide thumbs Also See for X6-2:
Table of Contents

Advertisement

Requirement
The minimum ceiling height for the cabinet is 230 cm (90 inches), measured from the true floor
or raised floor, whichever is higher. An additional 91.4 cm (36 inches) is for top clearance. The
space above the cabinet and its surroundings must not restrict the movement of cool air between
the air conditioner and the cabinet, or the movement of hot air coming out of the top of the
cabinet.

Maintenance Space Requirements

The maintenance area for the rackmounted Oracle Exadata Storage Server X6-2 Extreme
Flash must have the required access space. The following table lists the maintenance access
requirements for the storage server when it is installed in a rack.
TABLE 7
Location
Rear of the storage server
Area above the rack
Front of the storage server

Configuration Restrictions

There are restrictions for adding servers to the Oracle Exadata Database Machine. The
following sections describe the restrictions for flexible configurations:
"Exadata Database Machine X6-2 Configuration Restrictions" on page 21
"Exadata Storage Expansion Rack X6-2 Configuration Restrictions" on page 22

Exadata Database Machine X6-2 Configuration Restrictions

The following restrictions apply to Oracle Exadata Database Machine X6-2 flexible
configurations:
Up to 22 servers can be installed in the rack, within a total of 38 rack units.
Specification
Clearance, rear of storage server: 91.4 cm (36 inches)
Maintenance Access Requirements
Maintenance Access Requirement
91.4 cm (36 inches)
91.4 cm (36 inches)
123.2 cm (48.5 inches)
Maintenance Space Requirements
About Rack Installation
21