Huawei UPS5000-S-35K User Manual page 102

Singapore, 35 kva power modules
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Output Settings
Figure 4-24 Output settings
Issue 02 (2020-01-10)
Item
Description
Input cur.
Limits the input current to protect
limiting ratio
the D.G.
(%)
Item
Description
Output voltage
Specifies the system output
level
voltage level. This parameter is
configurable only after the
inverter shuts down. After you
change the voltage level, the
upper limit of the bypass voltage
restores to the default value. (If
the voltage level is 380 V or 400
V, the default upper limit is
+15%. If the voltage level is 415
V, the default upper limit is
+10%.)
Output volt.
The output voltage can be
adjustment (V)
slightly adjusted based on the
onsite power distribution
condition to ensure a minimum
difference between the output
voltage and the bypass voltage
and facilitate uninterruptible
power supply when the UPS
transfers from normal mode to
bypass mode.
Output
Specifies the system output
frequency (Hz)
frequency level.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
200%
50%–200%
Default Value
Value Range
400
380, 400, 415
The default
380 V: 209.0–
231.0
value is 220.0,
230.0, and 240.0
400 V: 218.5–
when the
241.5
voltage level is
415 V: 228.0–
380 V, 400 V,
252.0
and 415 V
respectively.
50 Hz
50 Hz, 60 Hz
94