5.2 Shutting Down and Powering Off the UPS

Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is not normal, the UPS supplies no power. Before shutting down the UPS, ensure
that all loads have shut down.
Procedure
Step 1 Shut down the inverter.
Issue 02 (2020-01-10)
On the LCD
On the main screen, tap Common Functions. Tap Inv. OFF.