Huawei UPS5000-S-35K User Manual page 194

Singapore, 35 kva power modules
Table of Contents

Advertisement

UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0022-1
No battery
0025-1
Battery
overvoltage
0026-1
Low battery
voltage
0530-1
Battery
ground fault
0032-1
Battery
overvoltage
Issue 02 (2020-01-10)
Cause
discharge.
Minor
There is no
battery string.
The battery string
is not properly
installed.
The power
module battery
fuse is blown.
Minor
The configured
number of
batteries is less
than the actual
number.
The battery
neutral wire is not
installed properly.
Minor
Battery discharge
results in low
battery voltage.
The battery
neutral wire is not
installed properly.
The charger is
faulty.
Critical
The battery string
is not properly
grounded.
The battery
ground
monitoring cable
is faulty.
The dry contact
board is faulty.
Critical
The battery
voltage is greater
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check that battery cables are
correctly connected.
2. Check that the battery terminal
voltage is normal.
3. Check that the battery fuse in the
power module is intact.
1. Check whether battery parameters
are correctly set.
2. If they are correctly set, certain
batteries may be faulty.
3. Check whether the battery neutral
wire is correctly connected.
1. If the low battery voltage alarm is
generated in battery mode, check
whether the mains voltage
recovers. If yes, charge batteries
immediately.
2. Check whether the battery neutral
wire is correctly connected.
3. If this alarm is generated in normal
mode, check whether the battery
switch is ON. If yes, the charger
may be faulty. Replace the related
power module.
1. Check whether the positive and
negative terminals of the battery
string are grounded or have
sufficient resistance to the ground.
2. Check whether the battery
grounding failure detector is faulty
by replacing it with a new one.
3. If no battery grounding failure
detector is available, check on the
dry contact board whether the
battery grounding failure detector
is enabled. If yes, disable it and
check whether the alarm is cleared.
If the alarm persists, the dry
contact board may be faulty.
Replace the board.
1. Check the battery voltage.
C Alarm List
186