UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Table 3-3 Cabinet power cable terminal requirements
Port
Connection
Description
Method
Mains input
Crimped OT
terminals
Bypass input
Crimped OT
terminals
Battery input
Crimped OT
terminals
Output
Crimped OT
terminals
PE
Crimped OT
terminals
Issue 02 (2020-01-10)
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the
neutral wires 1.5–1.7 times.
The nominal battery discharge current refers to the current at a voltage of 456 V when
thirty-eight 12 V batteries are configured.
The maximum battery discharge current refers to the current when thirty-eight 12 V
batteries, that is, two hundred and twenty-eight 2 V battery cells (1.75 V/cell), stop
discharging.
The battery cable specifications are selected based on 38 batteries and compatible with
application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure input power
cables as mains input power cables. In addition, cables listed in
the following conditions:
90° C flexible copper power cable. Multi-core cables are recommended for mains
and bypass input and output power cables, and single-core cables are recommended
for battery cables.
Routing mode: Mains and bypass input and output power cables are routed over a
ladder or bracket (E in IEC60364-5-52), and battery cables are routed over a ladder
or bracket in a single layer (F in IEC60364-5-52).
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
It is recommended that the AC power cable be no longer than 30 meters and the DC
power cable be no longer than 40 meters.
Bolt
Specifications
M12
M12
M12
M12
M12
Copyright © Huawei Technologies Co., Ltd.
Bolt Hole
Bolt Length
Diameter
13.5 mm
45 mm
13.5 mm
45 mm
13.5 mm
45 mm
13.5 mm
45 mm
13.5 mm
30 mm
3 Installation
Table 3-2
apply only to
Torque
46 N•m
46 N•m
46 N•m
46 N•m
46 N•m
49