UPS5000-S-(35 kVA-210 kVA)
User Manual (Singapore, 35 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0098-1
Bypass
current not
shared
0150-1
Inverter
asynchronous
0101-1
BSC signal
abnormal
0102-1
Maint.
breaker
misoperation
0380
In self-check
Issue 02 (2020-01-10)
Cause
The ECO bypass
voltage or
frequency range
is incorrectly set.
The bypass input
sequence is
reverse or the
neutral wire is
disconnected.
Minor
The output and
input circuit
breakers are OFF.
The length of the
bypass input or
output cables is
incorrect.
The bypass SCR
open-circuits.
Minor
The bypass
frequency
changes fast.
The output
frequency track
rate is incorrectly
set.
Minor
The dual bus
connector is
loose.
Parameters are set
incorrectly.
Critical
The user operation is
incorrect.
Warning
The inverter is in
self-check.
Copyright © Huawei Technologies Co., Ltd.
Solution
range, and frequency range are
correctly set.
3. Check that the bypass cables and
circuit breakers are correctly
connected.
1. Check that the output and bypass
input circuit breakers on each rack
are ON.
2. Check that bypass input and output
power cables on each rack meet
the length requirements.
3. Rectify any bypass SCR open-
circuit.
1. Check that the bypass output
frequency does not change fast.
2. Check that the Output freq. track
rate is properly set.
1. Check the dual bus connector.
2. Check the parameter settings.
3. The master BSC system is not
supplying power.
1. Shut down the inverter and then
close the maintenance circuit
breaker.
2. After maintenance, open the
maintenance circuit breaker and
then start the inverter.
Wait until the inverter self-check is
complete.