O Modules; Digital Input Modules; 750-433 [4 Di Dc 24 V 0.2 Ms / 2- Conductor]; View - WAGO 750-433 Manual

I/o system 750 fieldbus independent i/o modules
Table of Contents

Advertisement

2 I/O Modules

2.1 Digital Input Modules

2.1.1 750-433 [4 DI DC 24 V 0.2 ms / 2- conductor]

4- Channel Digital Input Module DC 24 V 0.2 ms,
2- conductor connection; high-side switching
2.1.1.1

View

Status
DI 1
DI 3
DI 1
DI 3
Fig. 2.1.1-1: 4- Channel Digital Input Module 750-433
2.1.1.2

Description

The digital input module 750-433 receives control signals from digital field
devices (sensors, etc.).
The module has four input channels. Four 2-conductor sensors may be directly
connected to the module.
The sensors can be connected using connection 24 V and DI 1 or DI 2, DI 3,
DI 4.
The connection of 3-conductor sensors to this module requires a field side
connection module (750-604 or 750-614) for 0 V supply.
Each input module has an RC noise rejection filter with a time constant of
0.2 ms.
The status of the input channels is indicated via status LEDs.
An optocoupler is used for electrical isolation between the bus and the field
side.
WAGO-I/O-SYSTEM 750
I/O Modules
750-433 [4 DI DC 24 V 0.2 ms / 2- conductor]
13 14
Status
A
DI 2
C
B
DI 4
D
13 14
Data contacts
DI 2
+
+
24V
+
+
24V
15 16
DI 4
750-433
Power jumper contacts
• 7
View
g043300e

Advertisement

Table of Contents
loading