RECYCLING AND DISPOSAL

TROUBLESHOOTING
Problem
The burner does not ignite when heat
is requested
The burner goes into lockout before or
during pre-purging
The burner performs pre-purging and
ignition correctly but locks out after
about 5 seconds
The burner starts up only after late
ignition.
4 RECYCLING AND DISPOSAL
The device is primarily composed of:
Material
Metal materials
ABS (acrylonitrile-butadiene-
styrene)
Glass wool felt
Electrical and electronic
components
At the end of the life cycle, safely remove the components and
dispose of them in a responsible manner, in compliance with
the installation country's applicable environmental legislation.
Diagnostic signal
OFF
GREEN, RED alternate
flashing
OFF
GREEN flashing
RED flashing
RED
Always ON
OFF
Component
Pipes, circulator, boiler body
Control panel enclosure
Boiler body insulation
Cables and wirings, regulator,
circulator
Probable cause
No electrical power
The flame detector reads
extraneous light
The burner controller
connectors are not
properly plugged in
Short circuit connector P
not connected
The flame detector is
reading extraneous light
Flame detector dirty
The flame detector is
faulty
The flame detaches or
fails
Ignition electrodes
incorrectly positioned
Air flow rate too high
Nozzle dirty or worn
9
Adequate sorted waste collection, processing and environ-
mentally-friendly disposal contribute to preventing possible
negative impacts on the environment and health and pro-
mote the reuse and/or recycling of the materials of which
the appliance consists.
9
Illegal disposal of the product by the owner shall be subject
to administrative fines provided for by applicable laws.
60
Remedy
Check voltage at L, N and
in power plug
Check the condition of
the fuses
Check that the safety
thermostat has not
tripped
Eliminate cause of light or
false flame signal
Make sure that all
connectors are properly
connected
Replace as necessary
Eliminate cause of light or
false flame signal
Clean the flame detector
Change as necessary
Check fuel oil pressure
and flow rate
Check the air flow
Change the nozzle
Check solenoid valve coil
Adjust ignition electrodes
as instructed in this
manual.
Adjust air flow rate as
instructed in this manual.
Replace