5 Operation

In case of co-existance of two or more of the following conditions:
 high ambient temperature
 High liquid temperature
 duty points insisting on unit maximum power
 persisting undervoltage of mains,
may jeopardise the life of the unit, and/or derating may occur: for further information contact
Xylem or the Authorised Distributor.

5.1 Wait times

WARNING: Electrical hazard
Contact with electric components may cause death, even after the unit has been switched off.
Before any interventions on the unit, the network voltage and any other input voltages must be
disconnected for the minimum time indicated in Table 9.
Table 9: Wait times
WARNING: Electrical hazard
Frequency converters contain DC-link capacitors that can remain charged even when the
frequency converter is not powered.
To avoid electrical hazards:
 Disconnect the AC power supply
 Disconnect all types of permanent magnet motors
 Disconnect all DC-link remote power supplies, including the battery backups, the
 Wait for the capacitors to discharge completely before carrying out any maintenance or
e-SM Drive model
103, 105, 107, 111, 115
303, 305, 307, 311, 315, 322
Uninterrupted Power Supply units and the DC-link connections to other frequency converters
repairs; see Table 9 for the waiting times
en – Original instructions
Minimum waiting times (min)
4
5
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

E-lneseE-lnteeE-lntse