User Adjustment & Diagnostic Menu - Neptronic SKE90 Installation Instructions Manual

Electric steam humidifier ske series ske-xl bacnet
Hide thumbs Also See for SKE90:
Table of Contents

Advertisement

HUM. INP
08
2-10 VDC
DU CT I N P
09
2 -1 0 VDC
SKB 3XX
10
NEP r1.5
Note:
1.
Any changes made in the Program Mode are saved into a non-volatile memory.
To enter to User adjustment & Diagnostic menu: press and hold
Seq
Display
#
SSR TmP
01
40 C
WTR TOFF
02
100 C
WTR FREQ
03
8000 Hz
WTR LOFF
04
100 %
FOAM PRB
05
207
Drn Tm Out
06
5 min
No Demnd
07
72 HRS
Hold Tmp
08
OFF
Anti-Frz
09
OFF
ALARM
10
Beep ON
T Unit
11
CELSIUS
CONTRAST
12
25
SKB 3xx
13
NEP r1.5
Humidity signal input selection.
Duct Humidity signal input selection.
Revision level of the program installed
User Adjustment & Diagnostic Menu
Type
Reading
SSR Temperature reading
User
Water temperature offset user adjustment
adjustment
Reading
Water level frequency reading
User
Water level offset user adjustment
adjustment
Reading
Foaming probe value reading
User
Drain time user adjustment
adjustment
Delay to drain out the humidifier from its
User
remains water when there is no demand, in
adjustment
order to prevent bacteria growth
User
Holding temperature of the evaporation
adjustment
chamber for fast response to demand
Anti-freezing temperature for the
User
evaporation chamber for humidifier to be
adjustment
installed in weather proof enclosure.
User
Alarm beep, to be selected ON or OFF
adjustment
User
Temperature unit scale Celsius or
adjustment
Fahrenheit
User
LCD Display contrast level
adjustment
Model of humidifier and revision number of
Reading
program installed.
SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual
(down) and then press
Description
26
0-10VDC, 2-10VDC,
0-20mA or 4-20mA
Default : 2-10VDC
0-10VDC, 2-10VDC,
0-20mA or 4-20mA
Default : 2-10VDC
N/A
(menu).
Value
N/A
Range: from -10˚C to +10˚C
Default: 0
N/A
Range: from -10% to +10%
Default: 0%
N/A
Range: from 4 to 16 min
Range: from 1 to 250 Hrs
Default: 72Hrs
Range: from 15 to 90˚C or OFF
Default: OFF
Range: from 4 to 10˚C or OFF
Default: OFF
Range: ON or OFF
Default: OFF
Range: Celsius or
Fahrenheit
Default: Celsius
Range: from 0 to 40
Default: 25 (legible LCD)
N/A