5 Installation
5.3 Interfaces
5.3.3
Wiring
28

Power supply

The device is provided with an internal fuse and is protected against polarity reversal. The functional
earthing terminal is connected exclusively to the connector cover and not to the 0 V. The housing is
made from plastic and is isolated. The device power supply is not electrically isolated.
The device requires a 24 VDC power supply from an AC/DC converter with safe isolation (SELV). For
other power supply requirements see Chapter 9.5.1 Power supply,
SELV (safety extra low voltage):
Circuit in which no dangerous voltage is present, even in the event of a single fault.
Fig. 10 Power supply interface
Phoenix Contact MSTB 2.5/3-ST-5.08 connector, Phoenix order no. 1757022 is supplied with the
device.
Fig. 11 Phoenix Contact MSTB 2.5/3-ST-5.08 connector (view from the wiring side)
Connection
+24 VDC
+24 VDC power supply
?
Functional earthing connected with connector cover.
Does not have to be connected.
This connection can be used as protective earthing connection if the
mounting environment requires this.
0 V
0 V power supply
Tab. 7 Assignment of connector
The following must be observed when the connector wiring is prepared:
Preparing the wiring of the connector
Terminal type
Pluggable screw terminal
Cross-section
Stripping length
7 mm
Max. tightening torque
Tab. 8 Preparing the wiring of the connector
XV-102 Micro Panel MN04802004Z-EN—February 2013 www.eaton.com
www.comoso.com
+24 VDC
0 V
Assignment
2
min. 0.75 mm
/ max. 2.5 mm
min. AWG18 / max. AWG12
0.6...0.8 Nm / 5...7 Lb. In.
69.