Parameter List
Variable
Category Add-
type
ress
D1 (91)
Can be
0100
Bank 1 Set Point - CH1
changed
0101
Bank 1 Proportional Band - CH1
during
operation.
0102
Bank 1 Integral Time - CH1
0103
Bank 1 Derivative Time - CH1
0104
Bank 1 SP Ramp Rise Value - CH1
0105
Bank 1 SP Ramp Fall Value - CH1
Not used.
0107
Bank 1 Manual Reset Value - CH1
0108
Bank 1 Cooling Coefficient - CH1
0109
Bank 1 Dead Band - CH1
Not used.
010D Bank 1 Alarm Value 1 - CH1
010E Bank 1 Alarm Upper Limit Value 1 - CH1
010F Bank 1 Alarm Lower Limit Value 1 - CH1
0110
Bank 1 Alarm Value 2 - CH1
0111
Bank 1 Alarm Upper Limit Value 2 - CH1
0112
Bank 1 Alarm Lower Limit Value 2 - CH1
0113
Bank 1 Alarm Value 3 - CH1
0114
Bank 1 Alarm Upper Limit Value 3 - CH1
0115
Bank 1 Alarm Lower Limit Value 3 - CH1
Not used.
0200
Bank 1 Set Point - CH2
0300
Bank 1 Set Point - CH3
0400
Bank 1 Set Point - CH4
Variable
Category Add-
type
ress
D2 (92)
Can be
0100
Bank 2 Set Point - CH1
changed
0101
Bank 2 Proportional Band - CH1
during
operation.
0102
Bank 2 Integral Time - CH1
0103
Bank 2 Derivative Time - CH1
0104
Bank 2 SP Ramp Rise Value - CH1
0105
Bank 2 SP Ramp Fall Value - CH1
Not used.
0107
Bank 2 Manual Reset Value - CH1
0108
Bank 2 Cooling Coefficient - CH1
0109
Bank 2 Dead Band - CH1
Not used.
010D Bank 2 Alarm Value 1 - CH1
010E Bank 2 Alarm Upper Limit Value 1 - CH1
010F Bank 2 Alarm Lower Limit Value 1 - CH1
0110
Bank 2 Alarm Value 2 - CH1
0111
Bank 2 Alarm Upper Limit Value 2 - CH1
0112
Bank 2 Alarm Lower Limit Value 2 - CH1
0113
Bank 2 Alarm Value 3 - CH1
0114
Bank 2 Alarm Upper Limit Value 3 - CH1
0115
Bank 2 Alarm Lower Limit Value 3 - CH1
Not used.
0200
Bank 2 Set Point - CH2
0300
Bank 2 Set Point - CH3
0400
Bank 2 Set Point - CH4
Note The decimal point position is determined by the sensor selection. With analog inputs, the decimal point
position is determined by the Decimal Point Position parameter setting. In this case, however, the 0 (****)
decimal point position setting will be treated as a setting of 1 (***.*).
Parameter name
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' 00000001 to H' 0000270F (1 to 9999)
H' 00000000 to H' 00000F9F (0 to 3999)
H' 00000000 to H' 0000270F (0.0 to 999.9)
H' 00000000 to H' 0000270F (0 to 9999)
(Function stops when set to 0.)
H' 00000000 to H' 0000270F (0 to 9999)
(Function stops when set to 0.)
H' 00000000 to H' 000003E8 (0.0 to 100.0)
H' 00000001 to H' 0000270F (0.01 to 99.99)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
The rest are the same as channel 1.
Parameter name
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' 00000001 to H' 0000270F (1 to 9999)
H' 00000000 to H' 00000F9F (0 to 3999)
H' 00000000 to H' 0000270F (0.0 to 999.9)
H' 00000000 to H' 0000270F (0 to 9999)
(Function stops when set to 0.)
H' 00000000 to H' 0000270F (0 to 9999)
(Function stops when set to 0.)
H' 00000000 to H' 000003E8 (0.0 to 100.0)
H' 00000001 to H' 0000270F (0.01 to 99.99)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
H' FFFFF831 to H' 0000270F (−1999 to 9999)
The rest are the same as channel 1.
Setting (monitor) range
Setting (monitor) range
Appendix
Defau-
Unit
Attribut-
Target Unit
lt
es
TC4/
HFU
TC2
0
EU
BANK
---
80
EU (See
BANK
---
note.)
233
Seconds BANK
---
40.0
Seconds BANK
---
0
EU/s or
BANK
---
EU/min
0
EU/s or
BANK
---
EU/min
50.0
%
BANK
---
1.00
---
BANK
---
0
EU (See
BANK
---
note.)
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
TC4
---
TC4
---
Defau-
Unit
Attribut-
Target Unit
lt
es
TC4/
HFU
TC2
0
EU
BANK
---
80
EU (See
BANK
---
note.)
233
Seconds BANK
---
40.0
Seconds BANK
---
0
EU/s or
BANK
---
EU/min
0
EU/s or
BANK
---
EU/min
50.0
%
BANK
---
1.00
---
BANK
---
0
EU (See
BANK
---
note.)
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
0
EU
BANK
---
TC4
---
TC4
---
197

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents