Omron EJ1 User Manual page 182

Modular temperature controller
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Detailed Description of Services
Response code
Error name
7014
Operation error
(7014)
7015
Operation error
(7015)
7016
Operation error
(7016)
7020
Operation error
(7020)
7021
Operation error
(7021)
7030
Operation error
(7030)
7041
Operation error
(7041)
7042
Operation error
(7042)
0000
Normal completion
Cause
The command cannot be executed because
EEPROM is currently being written.
Execute retries until the 7014 response code
is reset.
The command cannot be executed during
reset (including startup).
The command cannot be executed during
error latch status.
The command cannot be executed in the cur-
rent control mode.
The command cannot be executed because
the control switching conditions have not
been established.
The command cannot be executed in the cur-
rent output mode.
The command cannot be executed in manual
operation mode.
The command cannot be executed in tuning
mode.
Processing was completed normally.