Omron EJ1 User Manual page 112

Modular temperature controller
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Detecting Current Errors
Normal Operation
17.3 A
200 V
200 V
17.3 A
200 V
To CT input
17.3 A
Heater Burnout Occurred
Burnout
Load: Heater
(example)
200 V
200 V
15 A
200 V
To CT input
15 A
To CT input
Current when there is a burnout
2. Three-phase Heaters
a. Delta Connection
Example: Using Three 200-VAC, 2-kW Heaters
Load
CT
CT
To CT input
When each phase's current is normal, the current is:
17.3 A ( ≅
× 10 A).
3
Load
CT
CT
3
= 10 A ×
×
3
------ -
2
= 15 A
The heater burnout current when there is a burnout at the load line is as fol-
lows:
Heater burnout detection current =
The heater burnout current when there is a burnout at the load is as follows:
Heater burnout detection current =
To enable detection in either case, use 16.1 A as the heater burnout detection
current.
Load: Heater (example)
10 A
Load: Heater
(example)
200 V
200 V
17.3 A
200 V
To CT input
10 A
To CT input
Current when there is a burnout
17.3
+
15
------------------------
2
17.3
+
10
------------------------
2
Section 4-5
Burnout
Load
CT
CT
1
= 10 A ×
×
------ -
3
3
= 10 A
≅ 16.15 [A]
≅ 13.65 [A]
91