Omron EJ1 User Manual page 166

Modular temperature controller
Hide thumbs Also See for EJ1:
Table of Contents

Advertisement

Frame Configuration
BCC Calculation Example
Note
Response Frame
End Codes
End code
Name
0F
FINS command error The specified FINS command could not be executed.
10
Parity error
11
Framing error
12
Overrun error
13
BCC error
14
Format error
16
Sub-address error
18
Frame length error
00
Normal completion
STX
Unit No.
02H 30H
30H
BCC
=
30H 30H 30H 30H 30H 30H
:
XOR (exclusive OR) calculation
No response will be returned unless the frame contains all elements up to the
ETX and BCC.
Sub-address End code
STX
Unit No.
02H
1
2
Meaning
The OR of 1 bits in received data does not match the setting
for the communications parity.
Stop bit is 0.
The next data was received when the reception data buffer
was full.
The calculated BCC value is different from the received BCC
value.
The FINS-mini command text contains characters other than
0 to 9 and A to F. For details on the echoback test, refer to
6-4-10 Echoback Test.
SID and the FINS-mini command text are not included.
The sub-address is not included.
The received frame exceeds the specified number of bytes.
Command processing was completed normally.
End Code Example
When the Sub-address, SID, and FINS-mini Command Text Are Not Included
• Command
Unit No.
STX
ETX
02H
0
1
03H
• Response
Sub-address
STX
Unit No.
02H
0
1
0
The sub-address is "00" and the end code is "16" (sub-address error).
Sub-address SID
FINS-mini command text
30H 30H 30H 30H
35H 30H 30H 03H 36H
35H
Text
FINS-mini command text
0
0
2
2
BCC calculation range
BCC
End code
ETX
BCC
0
1
6
03H
Section 6-2
ETX BCC
30H 30H
03H = 36H
ETX BCC
03H
1
1
Error detection priority
8
2
1
3
5
7
6
4
None
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents