Bosch Rexroth AG
Interfaces
Wiring 400 V
Rexroth IndraControl VAM 11.1/41.1 Machine Control Panels
min. 16 mm ² ( green/yellow)
Leads
16 mm ² (green/yellow)
6 mm² ( green/yellow)
PE neutral point
Fuses, better: protective motor switches
Transformer
acc. to EN 60742
N-conductor:
4 mm ² (green/yellow)
Use only with
PE
permission of
the operator!
e.g. drives
230 V power supply
operator terminals
service plug receptacle(s)
Overvoltage category I
(1)
PE bars are to be installed preferably on the mounting plate.
In case of isolated PB bars, both ends must be connected to the mounting plate
by means of copper strips with a maximum length of 20 cm.
The cross-section of the copper strips has to be at least equal to that of the incoming cable.
Fig.7-7:
Wiring 400 V
DANGER
Connect power supply units, which generate protective extra-low voltage
(PELV) (24 V), only to supply voltages for which they are designed. Ob‐
serve the overvoltage categories, see
Do not apply the supply voltage to the protective extra-low voltage (PELV).
DOK-SUPPL*-VAM*11/41**-PR03-EN-P
To the housing of the control cabinet
To the machine
All housing parts (functional ground)
16 mm ² (green/yellow)
Overvoltage category III
4 mm ² (green/yellow)
400V
230V
(1)
N
U2
PE
4 mm ² (green/yellow)
Overvoltage category II
Power unit
Terminals in
DC 24 V
=
isolated
arrangement
Danger of death by high electric voltage
"Wiring 400 V" on page
Power unit
DC 24 V
U
U
Q
L
0 V U
0 V
U
Q
L
50.